Home › New Hampshire › Rochester Water Dept

Rochester, NH · EPA ID NH2001010

Rochester Water Dept drinking water records

👥25,000people served
⚠️3health-based violations since 2016
📋5total violations, all years
💧SWsurface water (lake, river or reservoir)
Quick answer

Rochester Water Dept has had 3 health-based violations since 2016 in EPA records, most recently Haloacetic acids (HAA5, a disinfection byproduct) (Contaminant level above the legal limit) starting 2022-01-01. It serves about 25,000 people in Rochester, NH using surface water (lake, river or reservoir). Total violations on record (all years, including paperwork): 5. 2 are not yet marked resolved.

No safety score. TapWaterPro does not rate water as safe or unsafe. Pages list official EPA records: measured results, legal limits and violations, with dates and sources. Detection vs violation

Lead and copper tap sampling

Under EPA's Lead and Copper Rule the system samples taps in homes, and reports the 90th-percentile result: 90% of homes tested were at or below this level. A result above the action level (lead 0.015 mg/L, copper 1.3 mg/L) is not itself a violation; it requires the system to take extra steps. A violation happens when a required step or test is missed.

Sampling periodMetal90th percentileAction levelAbove action level?
2021-01-01 to 2023-12-31Lead0.002 mg/L0.015 mg/LNo
2018-01-01 to 2020-12-31Lead0 mg/L0.015 mg/LNo
2015-01-01 to 2017-12-31Lead0.002 mg/L0.015 mg/LNo

Lead often comes from a home's own service line, solder or fixtures, so your tap can differ from these results. Only a test of your own tap tells you what is in it.

Data dates

Official system nameROCHESTER WATER DEPT
EPA system ID (PWSID)NH2001010
Latest lead/copper sampling period2021-01-01 to 2023-12-31
Latest violation period in record2022-01-01
Published byNH DES, reported to EPA SDWIS/Fed (quarterly)
Imported by TapWaterProOctober 30, 2026
VerifiedChecked against the EPA Envirofacts record on October 30, 2026; not an independent water test

System facts

EPA system IDNH2001010
Population served25,000
Service connections7,500
Water sourcesurface water (lake, river or reservoir)
Owner typelocal government
Town / countyRochester, Strafford County

Violations since 2016, in plain words

"Health-based" means a contaminant went over a legal limit or a required treatment step was missed. Monitoring and reporting violations mean a test or report was late or missing; they do not by themselves mean the water was unsafe.

Full violation history

Period beganWhatTypeMeasured / legal limitHealth-based?Status
2022-01-01Haloacetic acids (HAA5, a disinfection byproduct)Contaminant level above the legal limit0.061 mg/L / 0.060 mg/LYesResolved 2022-07-06
2017-03-27Public notice ruleNotice or paperwork requirement missed—NoOpen
2016-12-08Public notice ruleNotice or paperwork requirement missed—NoOpen
2016-10-01Total trihalomethanes (TTHM, a disinfection byproduct)Contaminant level above the legal limit0.082 mg/L / 0.080 mg/LYesResolved 2017-07-11
2016-07-01Total trihalomethanes (TTHM, a disinfection byproduct)Contaminant level above the legal limit0.09 mg/L / 0.080 mg/LYesResolved 2017-07-11