Rochester, NH · EPA ID NH2001010
Rochester Water Dept drinking water records
Rochester Water Dept has had 3 health-based violations since 2016 in EPA records, most recently Haloacetic acids (HAA5, a disinfection byproduct) (Contaminant level above the legal limit) starting 2022-01-01. It serves about 25,000 people in Rochester, NH using surface water (lake, river or reservoir). Total violations on record (all years, including paperwork): 5. 2 are not yet marked resolved.
Lead and copper tap sampling
Under EPA's Lead and Copper Rule the system samples taps in homes, and reports the 90th-percentile result: 90% of homes tested were at or below this level. A result above the action level (lead 0.015 mg/L, copper 1.3 mg/L) is not itself a violation; it requires the system to take extra steps. A violation happens when a required step or test is missed.
| Sampling period | Metal | 90th percentile | Action level | Above action level? |
|---|---|---|---|---|
| 2021-01-01 to 2023-12-31 | Lead | 0.002 mg/L | 0.015 mg/L | No |
| 2018-01-01 to 2020-12-31 | Lead | 0 mg/L | 0.015 mg/L | No |
| 2015-01-01 to 2017-12-31 | Lead | 0.002 mg/L | 0.015 mg/L | No |
Lead often comes from a home's own service line, solder or fixtures, so your tap can differ from these results. Only a test of your own tap tells you what is in it.
Data dates
| Official system name | ROCHESTER WATER DEPT |
|---|---|
| EPA system ID (PWSID) | NH2001010 |
| Latest lead/copper sampling period | 2021-01-01 to 2023-12-31 |
| Latest violation period in record | 2022-01-01 |
| Published by | NH DES, reported to EPA SDWIS/Fed (quarterly) |
| Imported by TapWaterPro | October 30, 2026 |
| Verified | Checked against the EPA Envirofacts record on October 30, 2026; not an independent water test |
System facts
| EPA system ID | NH2001010 |
|---|---|
| Population served | 25,000 |
| Service connections | 7,500 |
| Water source | surface water (lake, river or reservoir) |
| Owner type | local government |
| Town / county | Rochester, Strafford County |
Violations since 2016, in plain words
- 3 × Contaminant level above the legal limit
- 2 × Notice or paperwork requirement missed
"Health-based" means a contaminant went over a legal limit or a required treatment step was missed. Monitoring and reporting violations mean a test or report was late or missing; they do not by themselves mean the water was unsafe.
Full violation history
| Period began | What | Type | Measured / legal limit | Health-based? | Status |
|---|---|---|---|---|---|
| 2022-01-01 | Haloacetic acids (HAA5, a disinfection byproduct) | Contaminant level above the legal limit | 0.061 mg/L / 0.060 mg/L | Yes | Resolved 2022-07-06 |
| 2017-03-27 | Public notice rule | Notice or paperwork requirement missed | — | No | Open |
| 2016-12-08 | Public notice rule | Notice or paperwork requirement missed | — | No | Open |
| 2016-10-01 | Total trihalomethanes (TTHM, a disinfection byproduct) | Contaminant level above the legal limit | 0.082 mg/L / 0.080 mg/L | Yes | Resolved 2017-07-11 |
| 2016-07-01 | Total trihalomethanes (TTHM, a disinfection byproduct) | Contaminant level above the legal limit | 0.09 mg/L / 0.080 mg/L | Yes | Resolved 2017-07-11 |
What you can do
- Read the system's annual Consumer Confidence Report (water quality report); systems must mail or post it each year. You can also ask Rochester Water Dept for it directly.
- If your home was built before 1986, lead can come from your own pipes and fixtures even when the utility's water is fine. Run the tap 30 seconds to 2 minutes before drinking if water sat for hours, and use cold water for cooking.
- If you want extra protection, choose a filter certified to NSF/ANSI 53 (lead) or 58 (reverse osmosis); a simple carbon filter certified to NSF/ANSI 42 helps mainly with chlorine taste.
- Surface water systems use disinfection, which creates byproducts (TTHM, HAA5) that are tested regularly.
- On a private well? This system's results do not apply to you. NH DES recommends yearly bacteria and nitrate tests and a Standard Analysis every 3-5 years. Private well guide